Troubleshooting Guide

Quick Checks

Before detailed troubleshooting, verify these basic items:

Communication Issues

PLC Connection Failed

Symptom: Status bar shows "PLC: Disconnected" (red)
Possible Causes:
  • Network cable disconnected or faulty
  • Wrong IP address configured
  • PLC powered off or in STOP mode
  • Firewall blocking port 502
Solutions:
  1. Ping the PLC IP address from command prompt
  2. Verify IP address in Settings > PLC Configuration
  3. Check PLC power and status LEDs
  4. Verify firewall allows port 502 (Modbus TCP)
  5. Check network switch and cables

Scanner Connection Failed

Symptom: Status bar shows "Scanner: Disconnected" (red)
Possible Causes:
  • QCS system not responding
  • Wrong IP address or port
  • Modbus server not enabled on QCS
Solutions:
  1. Ping the QCS/scanner IP address
  2. Verify configuration in Settings > Scanner Configuration
  3. Check QCS system is operating normally
  4. Confirm Modbus TCP is enabled on QCS

Intermittent Connection

Symptom: Connection status fluctuates between connected and disconnected
Possible Causes:
  • Network congestion or packet loss
  • Faulty cable or connector
  • Timeout settings too short
Solutions:
  1. Increase connection timeout to 5000ms
  2. Replace network cables
  3. Use dedicated industrial network
  4. Check for duplicate IP addresses

Control Issues

Profile Not Improving

Symptom: Zones in AUTO mode but profile deviation not decreasing
Possible Causes:
  • Control gain too low
  • Zone mapping incorrect
  • Valves not responding
  • Response matrix not configured
Solutions:
  1. Increase control gain gradually (0.3 → 0.5)
  2. Verify zone mapping matches physical layout
  3. Test valves in manual mode
  4. Check response matrix configuration

Oscillating Profile

Symptom: Profile swings back and forth, valves constantly moving
Possible Causes:
  • Control gain too high
  • Control interval too short
  • Filter depth too low (noisy data)
Solutions:
  1. Reduce control gain (e.g., 0.5 → 0.3)
  2. Increase control interval (e.g., 60s → 90s)
  3. Increase filter depth (e.g., 0.2 → 0.4)
  4. Increase deadband setting

Zones Not Responding

Symptom: Setpoint changes but feedback doesn't follow
Possible Causes:
  • Zone in MANUAL or LOCAL mode
  • Valve stuck or faulty
  • PLC not processing setpoints
  • I/O module fault
Solutions:
  1. Verify zone is in AUTO mode
  2. Check valve manually at the headbox
  3. Monitor PLC program execution
  4. Check I/O module diagnostics

Profile Issues

Profile All Zeros

Symptom: Profile display shows flat line at zero
Solutions:
  1. Verify scanner is traversing (not parked)
  2. Check register addresses in scanner configuration
  3. Verify data type (Float vs Integer)
  4. Check "Profile Valid" flag from QCS

Profile Values Wrong

Symptom: Profile values are very large, very small, or negative when they shouldn't be
Solutions:
  1. Toggle byte order setting (Big/Little Endian)
  2. Toggle word order setting
  3. Verify data type matches QCS output
  4. Check scaling factor if using integers

Profile Inverted or Offset

Symptom: Profile appears mirrored or shifted from actual position
Solutions:
  1. Toggle mapping direction (Front-to-Back vs Back-to-Front)
  2. Adjust front/back side offsets
  3. Verify databox count matches QCS

Actuator Issues

Valve Not Moving

Check List:
  1. Verify pneumatic air supply is on
  2. Check I/P converter operation
  3. Verify analog output signal at PLC
  4. Inspect valve for mechanical binding
  5. Check feedback potentiometer

Feedback Mismatch

Symptom: Large difference between setpoint and feedback
Solutions:
  1. Calibrate valve feedback sensor
  2. Check for mechanical problems
  3. Verify feedback scaling in PLC
  4. Check feedback wiring

Getting Support

Contact PowerFlow

For technical support with the Dilution Control System:

Information to Include:

  • Company name and mill location
  • Software version number
  • Description of the problem
  • Error messages (screenshots if possible)
  • Steps already tried
  • Configuration details (QCS type, PLC type)