Alarm Code Reference

Communication Alarms

Code Severity Message Cause & Action
COMM-001 Critical PLC Connection Lost Network failure or PLC offline. Check network cable, PLC power, and IP settings.
COMM-002 High QCS Connection Timeout Scanner data not received. Verify QCS network and DIU connection.
COMM-003 Medium Communication Slow Response time exceeds threshold. Check network load and switch capacity.
COMM-004 High Modbus Read Error Register read failed. Verify slave ID and register addresses.
COMM-005 High Modbus Write Error Register write failed. Check PLC write permissions.
COMM-006 Medium Reconnection Attempt System attempting to reconnect. Monitor for success.

Actuator Alarms

Code Severity Message Cause & Action
ACT-001 High Valve Not Responding Zone {N} not tracking setpoint. Check valve connection and air supply.
ACT-002 Medium Position Limit Reached Zone {N} at operating limit. May indicate profile issue or limit too restrictive.
ACT-003 Medium Feedback Deviation Zone {N} feedback differs from setpoint. Possible valve or sensor issue.
ACT-004 Low Zone In Manual Mode Zone {N} not under automatic control. Intentional or needs attention.
ACT-005 High Valve Stuck Zone {N} not moving despite commands. Perform valve flush or manual check.
ACT-006 Medium Bending Limit Exceeded Zone {N} position limited by neighbor. Normal constraint behavior.

Profile Alarms

Code Severity Message Cause & Action
PROF-001 High Invalid Profile Data Scanner data out of range or corrupt. Check QCS sensor calibration.
PROF-002 Medium Edge Detection Failed Cannot determine web edges. Verify profile and edge threshold settings.
PROF-003 Medium Profile Stale No new profile data received. Check scanner operation and communication.
PROF-004 Low Spike Detected Outlier removed from profile. May indicate sensor or process issue.
PROF-005 Medium Profile Width Changed Detected web width change. Verify sheet width and edge detection.

Control Alarms

Code Severity Message Cause & Action
CTRL-001 High 2-Sigma High Profile variation exceeds threshold. Check control parameters and valve operation.
CTRL-002 Medium Control Disabled Automatic control not active. Check mode and enable conditions.
CTRL-003 Medium Control Oscillating Detected oscillation pattern. Reduce control gain.
CTRL-004 Low Target Changed Target profile or basis weight changed. Informational.
CTRL-005 Medium Control Timeout Control cycle exceeded time limit. Check system performance.

System Alarms

Code Severity Message Cause & Action
SYS-001 High License Expiring License expires in {N} days. Contact PowerFlow for renewal.
SYS-002 Critical License Expired License no longer valid. Control disabled until renewed.
SYS-003 Medium Disk Space Low Log storage space limited. Archive or delete old logs.
SYS-004 Low Configuration Saved System configuration saved. Informational.
SYS-005 Medium Database Error Data storage issue. Check disk and database integrity.
SYS-006 Low Application Started System startup completed. Informational.
Need Help?

For persistent alarms that cannot be resolved, contact PowerFlow Technical Support with the alarm code and any relevant system logs.