This guide assumes you have completed the Installation and License Activation steps. Ensure the control PC is connected to the industrial network.
Connect to PLC
Configure the connection to your PLC or valve controller.
- Launch the Dilution Control System
- Go to Settings > Connection
- Select your PLC Type:
- Modbus TCP - Generic controllers, Festo CPX
- Siemens S7 - Siemens S7-1200/1500
- Beckhoff - Beckhoff EK9000, TwinCAT
- Enter the IP Address of the PLC
- Configure the Port (default: 502 for Modbus)
- Click Test Connection to verify
- Click Save when successful
Example: Modbus TCP Configuration
| Protocol | Modbus TCP |
| IP Address | 192.168.1.100 |
| Port | 502 |
| Slave ID | 1 |
Configure Actuator Zones
Set up the dilution valve configuration to match your headbox.
- Go to Settings > Actuator Configuration
- Set the Number of Zones (typically 24-96)
- Configure zone parameters:
- Minimum Position: 0% (fully closed)
- Maximum Position: 100% (fully open)
- Stepping Limit: Maximum change per cycle (e.g., 5%)
- Set register addresses if required (see PLC Integration)
- Click Save Configuration
Example: 48-Zone Configuration
| Number of Zones | 48 |
| Min Position | 0% |
| Max Position | 100% |
| Stepping Limit | 5% per cycle |
| Bending Limit | 10% difference |
Connect QCS Scanner
Configure the connection to your QCS/scanner system for profile data.
- Go to Settings > Scanner Configuration
- Select your Scanner Type:
- ABB DIU / Accuray AC6
- Honeywell Experion
- Valmet / Metso IQ
- Yokogawa CENTUM
- JASCH
- Generic Modbus
- Enter the scanner IP Address and Port
- Configure Profile Settings:
- Databoxes: Number of measurement points (e.g., 200)
- Update Rate: Profile update interval
- Set Zone Mapping (front/back offsets)
- Click Test to verify profile reception
- Click Save
Example: Generic QCS Configuration
| Interface | Modbus TCP |
| IP Address | 192.168.1.50 |
| Port | 502 |
| Databoxes | 200 |
| Profile Register | 1000 |
Test in Manual Mode
Before enabling automatic control, verify the system works correctly in manual mode.
- Ensure the system is in Manual Mode (global mode selector)
- Select a single zone in the Zone Control Panel
- Manually adjust the setpoint:
- Increase position by 10%
- Verify the valve moves (check feedback)
- Observe the effect on the profile
- Test several zones across the web width
- Verify the profile responds in the correct direction:
- Increasing dilution should decrease basis weight
- Decreasing dilution should increase basis weight
Manual valve adjustments will affect paper quality. Coordinate with the paper machine operator before testing. Make small, gradual changes.
Enable Automatic Control
After successful manual testing, enable automatic control for profile uniformity.
- Set initial Control Parameters:
Control Mode Integrating (recommended) Control Gain 0.3 (conservative start) Deadband 1.0 g/m² Control Interval 60 seconds - Set the Target Profile:
- Use the profile average as the initial target, OR
- Set a flat target at the desired basis weight
- Switch individual zones to AUTO mode:
- Start with center zones first
- Gradually add edge zones
- Monitor the system response:
- Watch the error profile decrease
- Verify valves are adjusting gradually
- Check for oscillations (reduce gain if necessary)
- Once stable, switch Global Mode to AUTO
Start with low gain (0.2-0.3) and gradually increase until satisfactory response. See Gain Tuning for detailed guidance.
Next Steps
After completing the quick start, explore these topics for optimal performance: